logo

• Pumps, Boosters, Fire-fighting systems
• Agents, Importers, Manufacturers
iso

  

  flag-en

banner

Products > Booster sets > MPC-P H Booster sets with horizontal pumps and membrane pressure tank

 



MPC H2

jpeg Zoom picture
pdf Genral brochure (3,4 MB)
pdf Manual
pdf CE Declaration
   
























MPC H
A complete range of fully automatic twin booster sets for high-rise buildings, industries, hotels, hospitals, schools and all cases where a regula supply of water is of the utmost importance.
Suitability
The carefully studied design of our systems provides the best solution not only in ordinary cases but also in particular and complex ones, in the most efficient and cost effective way.
Reliability
The meticulous selection of the components and materials, the attention given to the minute detail, the rigid quality control applied before delivery and our unparalleled experience acquired through the manufacturing and installation of thousands of systems, have created the great reputation of the MPC H for efficiency and reliability.
Easy installation
The unique design of our systems enables easy transportation, saves space and time and permits an extremely simple installation. It is only required to connect its manifolds to the main pipes and electric power to the panel.
Low maintenance
The high quality control instruments in conjunction with the full autonomy of the safety mechanisms minimize the need for maintenance to the periodical routine inspection.
Service
Our experienced and highly qualified scientific and technical personnel is at your disposal and will gladly provide expert advice and technical assistance before and after sale, wherever you may be located.

Twin booster sets GRUPPI made by MARCO PUMPS

Each system consists of two pumps DAB-EBARA/ITALY. Pumps are fully assembled on common base withsuction and discharge manifolds, electric control panel and pressure tank. Automatic pump changeover, main switch and provision for connection of dry running protection float switch. For proper pressure tank sizing click here.


Type
Voltage

Power

Current

Manifolds

Dimensions

Weight

Performance of each pump

KW x 2

HP x 2

A x 2

In

Out

L x W x H (cm)

kg

 
With DAB K 2-stage
       
m3/h>
9
12
18
24
30
MPC-P H2 Κ70/300
3~400V
5.5
7.5
12.9
DN80
DN80
130 x 100 x 150
340
72
69
60
43
MPC-P H2 Κ80/300
3~400V
7.5
10
15
DN80
DN80
130 x 100 x 150
355
Η
91
89.5
82
68
MPC-P H2 Κ70/400
3~400V
9.2
12.5
18
DN80
DN80
130 x 100 x 150
360
(m)
84
82
76
65
47
MPC-P H2 Κ80/400
3~400V
11
15
21
DN80
DN80
130 x 100 x 150
365
95
94
89
80
64
                             
With DAB K 1-stage
               
m3/h>
6
9
12
15
18
MPC-P H2 K40/200T
3~400V
3
4
6.4
2 1/2"
2 1/2"
100 x 70 x 130
240
Η
40.5
39
37
33.5
29
MPC-P H2 K55/200T
3~400V
4
5.5
9.4
2 1/2"
2 1/2"
100 x 70 x 130
242
(m)
54
53.2
51.5
48.5
45
 
m3/h>
12
15
18
24
30
MPC-P H2 K28/500T
3~400V
4
5.5
8.5
DN80
DN80
100 x 70 x 150
260
Η
34.5
34
32.8
29
25
MPC-P H2 K40/400T
3~400V
5.5
7.5
11.5
DN80
DN80
130 x 100 x 150
513
(m)
49
48
45
37
24
MPC-P H2 K50/400T
3~400V
7.5
10
15
DN80
DN80
130 x 100 x 150
525
61
60
59
54.5
46
       
m3/h>
24
36
60
72
90
MPC-P H2 K30/800T
3~400V
7.5
10
14
DN100
DN100
130 x 110 x 150
594
42
38
21.5
MPC-P H2 K40/800T
3~400V
9.2
12.5
18
DN100
DN100
130 x 110 x 150
630
50
47
32.5
21
MPC-P H2 K50/800T
3~400V
11
15
20.5
DN100
DN100
130 x 110 x 150
648
Η
56.5
53.5
41
31
MPC-P H2 EN40-250
3~400V
15
20
27.5
DN100
DN100
150 x 110 x 170
734
(m)
72
68
56
MPC-P H2 EN50-200
3~400V
15
20
27.5
DN100
DN100
150 x 110 x 170
820
55.5
51
47.5
41
MPC-P H2 EN40-250
3~400V
18.5
25
33.5
DN100
DN100
150 x 110 x 170
814
82.5
80
67.5
58.5
MPC-P H2 EN50-200
3~400V
18.5
25
33.5
DN100
DN100
150 x 110 x 170
850
62
58
55
48.5
MPC-P H2 EN40-250
3~400V
22
30
39.5
DN100
DN100
150 x 110 x 170
840
94.5
92
81
71.5
MPC-P H2 EN50-250
3~400V
22
30
39.5
DN100
DN100
150 x 110 x 170
978
73
72
69
65
57
MPC-P H2 EN50-250
3~400V
30
40
52,5
DN100
DN100
150 x 110 x 170
1160
92
91
89
86
78
                             
With EBARA 2-stage
       
m3/h>
2.4
4.8
7.2
9
12.6
MPC-P H2 2CDX 70/10
3~400V
0.75
1
2.6
2"
2"
90 X 70 X 130
53
 
35
27
MPC-P H2 2CDX 120/15
3~400V
1.1
1.5
3.4
2 1/2"
2 1/2"
90 X 70 X 130
60
 
43
39.5
35
31
MPC-P H2 2CDX 120/20
3~400V
1.5
2
4.4
2 1/2"
2 1/2"
90 X 70 X 130
63
Η
51.5
47
42
37.5
MPC-P H2 2CDX 120/30
3~400V
2.2
3
5
2 1/2"
2 1/2"
90 X 70 X 130
76
(m)
59.3
54.6
49
44
MPC-P H2 2CDX 200/30
3~400V
2.2
3
6
2 1/2"
2 1/2"
90 X 70 X 130
80
 
53.5
51
48
45.5
40
MPC-P H2 2CDX 120/40
3~400V
3
4
6.2
2 1/2"
2 1/2"
90 X 70 X 130
83
 
68.5
64
57.5
52
MPC-P H2 2CDX 200/40
3~400V
3
4
6.6
2 1/2"
2 1/2"
90 X 70 X 130
80
 
64
61
58
55
49.3
MPC-P H2 2CDX 200/50
3~400V
4
5.5
8.7
2 1/2"
2 1/2"
90 X 70 X 130
95
 
72.8
70
67
64
57.8
                             
With EBARA 1-stage
       
m3/h>
6
9
12
15
20
MPC-P H2 3Μ 32-200/3
3~400V
3
4
DN80
DN80
130 Χ 100 Χ 150
118
42.5
41
38,5
35
29
MPC-P H2 3Μ 32-200/4
3~400V
4
5.5
DN80
DN80
130 Χ 100 Χ 150
133
m
53
51.5
49.5
47
40.5
MPC-P H2 3Μ 32-200/5.5
3~400V
5.5
7.5
DN80
DN80
130 Χ 100 Χ 150
155
69
67.6
65.5
63
56
       
m3/h>
12
20
27
33
42
MPC-P H2 3Μ 40-200/5.5
3~400V
5.5
7.5
DN100
DN100
130 Χ 100 Χ 150
216
46
43.5
41
38.5
33
MPC-P H2 3Μ 40-200/7.5
3~400V
7.5
10
DN100
DN100
130 Χ 100 Χ 150
230
m
56.5
55
52.5
49.8
45
MPC-P H2 3Μ 40-200/11
3~400V
11
15
DN100
DN100
130 Χ 100 Χ 150
294
71
68.8
66.2
63.5
58
       
m3/h>
30
39
48
60
72
MPC-P H2 3Μ 50-200/5.5
3~400V
5.5
7.5
DN100
DN100
150 Χ 100 Χ 150
269
50
48.4
46
41
34
MPC-P H2 3Μ 50-200/7.5
3~400V
7.5
10
DN100
DN100
150 Χ 100 Χ 150
306
m
56
54.5
52
48
42
MPC-P H2 3Μ 50-200/11
3~400V
11
15
DN100
DN100
150 Χ 100 Χ 150
360
70
68.5
66
62
57

MPC H2 K55/200T
MPC H2 2CDX
MPC-P H2 K55/200T
MPC-P H2 K50/400T
MPC-P H2 2CDX
     
All above systems are also availabe with 3 pumps (MPC H3 series ) or 4 pumps (MPC H4 series)

© Marco Pumps SA - P. Marcomichalis & Son SA  Tel +30 210 4830329 • Fax +30 210 4833358 •  sales@marcopumps.gr       youtube