• Pumps, Boosters, Fire-fighting systems • Agents, Importers, Manufacturers |
![]() |
Products > Booster sets > MPC-P H Booster sets with horizontal pumps and membrane pressure tank |
|
|
|
| Twin booster sets GRUPPI made by MARCO PUMPS |
Each system consists of two pumps DAB-EBARA/ITALY. Pumps are fully assembled on common base withsuction and discharge manifolds, electric control panel and pressure tank. Automatic pump changeover, main switch and provision for connection of dry running protection float switch. For proper pressure tank sizing click here. |
Type |
Voltage |
Power |
Current |
Manifolds |
Dimensions |
Weight |
Performance of each pump |
|||||||
KW x 2 |
HP x 2 |
A x 2 |
In |
Out |
L x W x H (cm) |
kg |
||||||||
With DAB K 2-stage |
||||||||||||||
m3/h> |
9 |
12 |
18 |
24 |
30 |
|||||||||
| MPC-P H2 Κ70/300 | 3~400V |
5.5 |
7.5 |
12.9 |
DN80 |
DN80 |
130 x 100 x 150 |
340 |
72 |
69 |
60 |
43 |
||
| MPC-P H2 Κ80/300 | 3~400V |
7.5 |
10 |
15 |
DN80 |
DN80 |
130 x 100 x 150 |
355 |
Η |
91 |
89.5 |
82 |
68 |
|
| MPC-P H2 Κ70/400 | 3~400V |
9.2 |
12.5 |
18 |
DN80 |
DN80 |
130 x 100 x 150 |
360 |
(m) |
84 |
82 |
76 |
65 |
47 |
| MPC-P H2 Κ80/400 | 3~400V |
11 |
15 |
21 |
DN80 |
DN80 |
130 x 100 x 150 |
365 |
95 |
94 |
89 |
80 |
64 |
|
With DAB K 1-stage |
||||||||||||||
m3/h> |
6 |
9 |
12 |
15 |
18 |
|||||||||
| MPC-P H2 K40/200T | 3~400V |
3 |
4 |
6.4 |
2 1/2" |
2 1/2" |
100 x 70 x 130 |
240 |
Η |
40.5 |
39 |
37 |
33.5 |
29 |
| MPC-P H2 K55/200T | 3~400V |
4 |
5.5 |
9.4 |
2 1/2" |
2 1/2" |
100 x 70 x 130 |
242 |
(m) |
54 |
53.2 |
51.5 |
48.5 |
45 |
m3/h> |
12 |
15 |
18 |
24 |
30 |
|||||||||
| MPC-P H2 K28/500T | 3~400V |
4 |
5.5 |
8.5 |
DN80 |
DN80 |
100 x 70 x 150 |
260 |
Η |
34.5 |
34 |
32.8 |
29 |
25 |
| MPC-P H2 K40/400T | 3~400V |
5.5 |
7.5 |
11.5 |
DN80 |
DN80 |
130 x 100 x 150 |
513 |
(m) |
49 |
48 |
45 |
37 |
24 |
| MPC-P H2 K50/400T | 3~400V |
7.5 |
10 |
15 |
DN80 |
DN80 |
130 x 100 x 150 |
525 |
61 |
60 |
59 |
54.5 |
46 |
|
m3/h> |
24 |
36 |
60 |
72 |
90 |
|||||||||
| MPC-P H2 K30/800T | 3~400V |
7.5 |
10 |
14 |
DN100 |
DN100 |
130 x 110 x 150 |
594 |
42 |
38 |
21.5 |
|||
| MPC-P H2 K40/800T | 3~400V |
9.2 |
12.5 |
18 |
DN100 |
DN100 |
130 x 110 x 150 |
630 |
50 |
47 |
32.5 |
21 |
||
| MPC-P H2 K50/800T | 3~400V |
11 |
15 |
20.5 |
DN100 |
DN100 |
130 x 110 x 150 |
648 |
Η |
56.5 |
53.5 |
41 |
31 |
|
| MPC-P H2 EN40-250 | 3~400V |
15 |
20 |
27.5 |
DN100 |
DN100 |
150 x 110 x 170 |
734 |
(m) |
72 |
68 |
56 |
||
| MPC-P H2 EN50-200 | 3~400V |
15 |
20 |
27.5 |
DN100 |
DN100 |
150 x 110 x 170 |
820 |
55.5 |
51 |
47.5 |
41 |
||
| MPC-P H2 EN40-250 | 3~400V |
18.5 |
25 |
33.5 |
DN100 |
DN100 |
150 x 110 x 170 |
814 |
82.5 |
80 |
67.5 |
58.5 |
||
| MPC-P H2 EN50-200 | 3~400V |
18.5 |
25 |
33.5 |
DN100 |
DN100 |
150 x 110 x 170 |
850 |
62 |
58 |
55 |
48.5 |
||
| MPC-P H2 EN40-250 | 3~400V |
22 |
30 |
39.5 |
DN100 |
DN100 |
150 x 110 x 170 |
840 |
94.5 |
92 |
81 |
71.5 |
||
| MPC-P H2 EN50-250 | 3~400V |
22 |
30 |
39.5 |
DN100 |
DN100 |
150 x 110 x 170 |
978 |
73 |
72 |
69 |
65 |
57 |
|
| MPC-P H2 EN50-250 | 3~400V |
30 |
40 |
52,5 |
DN100 |
DN100 |
150 x 110 x 170 |
1160 |
92 |
91 |
89 |
86 |
78 |
|
With EBARA 2-stage |
||||||||||||||
m3/h> |
2.4 |
4.8 |
7.2 |
9 |
12.6 |
|||||||||
| MPC-P H2 2CDX 70/10 | 3~400V |
0.75 |
1 |
2.6 |
2" |
2" |
90 X 70 X 130 |
53 |
35 |
27 |
||||
| MPC-P H2 2CDX 120/15 | 3~400V |
1.1 |
1.5 |
3.4 |
2 1/2" |
2 1/2" |
90 X 70 X 130 |
60 |
43 |
39.5 |
35 |
31 |
||
| MPC-P H2 2CDX 120/20 | 3~400V |
1.5 |
2 |
4.4 |
2 1/2" |
2 1/2" |
90 X 70 X 130 |
63 |
Η |
51.5 |
47 |
42 |
37.5 |
|
| MPC-P H2 2CDX 120/30 | 3~400V |
2.2 |
3 |
5 |
2 1/2" |
2 1/2" |
90 X 70 X 130 |
76 |
(m) |
59.3 |
54.6 |
49 |
44 |
|
| MPC-P H2 2CDX 200/30 | 3~400V |
2.2 |
3 |
6 |
2 1/2" |
2 1/2" |
90 X 70 X 130 |
80 |
53.5 |
51 |
48 |
45.5 |
40 |
|
| MPC-P H2 2CDX 120/40 | 3~400V |
3 |
4 |
6.2 |
2 1/2" |
2 1/2" |
90 X 70 X 130 |
83 |
68.5 |
64 |
57.5 |
52 |
||
| MPC-P H2 2CDX 200/40 | 3~400V |
3 |
4 |
6.6 |
2 1/2" |
2 1/2" |
90 X 70 X 130 |
80 |
64 |
61 |
58 |
55 |
49.3 |
|
| MPC-P H2 2CDX 200/50 | 3~400V |
4 |
5.5 |
8.7 |
2 1/2" |
2 1/2" |
90 X 70 X 130 |
95 |
72.8 |
70 |
67 |
64 |
57.8 |
|
With EBARA 1-stage |
||||||||||||||
m3/h> |
6 |
9 |
12 |
15 |
20 |
|||||||||
| MPC-P H2 3Μ 32-200/3 | 3~400V |
3 |
4 |
DN80 |
DN80 |
130 Χ 100 Χ 150 |
118 |
42.5 |
41 |
38,5 |
35 |
29 |
||
| MPC-P H2 3Μ 32-200/4 | 3~400V |
4 |
5.5 |
DN80 |
DN80 |
130 Χ 100 Χ 150 |
133 |
m |
53 |
51.5 |
49.5 |
47 |
40.5 |
|
| MPC-P H2 3Μ 32-200/5.5 | 3~400V |
5.5 |
7.5 |
DN80 |
DN80 |
130 Χ 100 Χ 150 |
155 |
69 |
67.6 |
65.5 |
63 |
56 |
||
m3/h> |
12 |
20 |
27 |
33 |
42 |
|||||||||
| MPC-P H2 3Μ 40-200/5.5 | 3~400V |
5.5 |
7.5 |
DN100 |
DN100 |
130 Χ 100 Χ 150 |
216 |
46 |
43.5 |
41 |
38.5 |
33 |
||
| MPC-P H2 3Μ 40-200/7.5 | 3~400V |
7.5 |
10 |
DN100 |
DN100 |
130 Χ 100 Χ 150 |
230 |
m |
56.5 |
55 |
52.5 |
49.8 |
45 |
|
| MPC-P H2 3Μ 40-200/11 | 3~400V |
11 |
15 |
DN100 |
DN100 |
130 Χ 100 Χ 150 |
294 |
71 |
68.8 |
66.2 |
63.5 |
58 |
||
m3/h> |
30 |
39 |
48 |
60 |
72 |
|||||||||
| MPC-P H2 3Μ 50-200/5.5 | 3~400V |
5.5 |
7.5 |
DN100 |
DN100 |
150 Χ 100 Χ 150 |
269 |
50 |
48.4 |
46 |
41 |
34 |
||
| MPC-P H2 3Μ 50-200/7.5 | 3~400V |
7.5 |
10 |
DN100 |
DN100 |
150 Χ 100 Χ 150 |
306 |
m |
56 |
54.5 |
52 |
48 |
42 |
|
| MPC-P H2 3Μ 50-200/11 | 3~400V |
11 |
15 |
DN100 |
DN100 |
150 Χ 100 Χ 150 |
360 |
70 |
68.5 |
66 |
62 |
57 |
||
![]() |
![]() |
![]() |
MPC-P H2 K55/200T |
MPC-P H2 K50/400T |
MPC-P H2 2CDX |
| All above systems are also availabe with 3 pumps (MPC H3 series ) or 4 pumps (MPC H4 series) | ||
| © Marco Pumps SA - P. Marcomichalis & Son SA • Tel +30 210 4830329 • Fax +30 210 4833358 • sales@marcopumps.gr |